@article{ajeee2017544,
author={{Chen, Yixi and Ju, Rong and Xu, Jie and Ma, Gang and Chen, Huaiyi and Xu, Guchao},
title={Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components},
journal={American Journal of Electrical and Electronic Engineering},
volume={5},
number={4},
pages={144--151},
year={2017},
url={http://pubs.sciepub.com/ajeee/5/4/4},
issn={2328-7357},
abstract={Resonant grounding system has been widely applied in low-voltage power systems all over the world. For the single-phase ground fault feeder-selection of resonant grounding system, the amplitude/phase comparison method of zero-sequence current which is used in traditional fault feeder-selection is not suitable to be used, due to the compensation action of arc suppression coil. In this paper, the electrical quantity changes after the single-phase ground fault of small current grounded system are analyzed firstly, therefore the reason why the amplitude/phase comparison method of zero-sequence current is not suitable to be used in resonant grounding system can be obtained. After that, based on zero-sequence current¡¯s multi-state components (transient component and steady component), a new fault feeder-selection method using double criteria is proposed, which not only can be applied in the single-phase ground fault of resonant grounding system but also has high reliability. At last, simulations based on MATLAB/Simulink are conducted to verify the validity of the method proposed in this paper.},
doi={10.12691/ajeee-5-4-4}
publisher={Science and Education Publishing}
}